Terminal
Signal
Description
11
NO2
Normally-open relay contact of the output NO2
12
NO3
Normally-open relay contact of the output NO3
13
R2..3
Output common for signals NO2 to NO3
Table 12: Assignment of the terminals for PM5032-T-ETH, PM5052-T-ETH and PM5072-
T-2ETH(W):
Terminal
Signal
Description
1
COM 0..11
Input common for digital input signals I0 to I11
2
I0
Digital input signal I0 (max. 5 kHz)
3
I1
Digital input signal I1 (max. 5 kHz)
4
I2
Digital input signal I2 (max. 5 kHz)
5
I3
Digital input signal I3 (max. 5 kHz)
6
I4
Digital input signal I4
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
7
I5
Digital input signal I5 (100 kHz)
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
8
I6
Digital input signal I6 (100 kHz)
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
9
I7
Digital input signal I7 (100 kHz)
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
10
I8
Digital input signal I8
11
I9
Digital input signal I9
12
I10
Digital input signal I10
13
I11
Digital input signal I11
14
O0
Digital output signal O0 (max. 5 kHz)
15
O1
Digital output signal O1 (max. 5 kHz)
16
O2
Digital output signal O2 (max. 5 kHz)
17
O3
Digital output signal O3 (max. 5 kHz)
18
O4
Digital output signal O4
PWM (max. 100 kHz), PTO (max. 200 kHz)
19
O5
Digital output signal O5
PWM (max. 100 kHz), PTO (max. 200 kHz)
20
O6
Digital output signal O6
PWM (max. 100 kHz), PTO (max. 200 kHz)
21
O7
Digital output signal O7
PWM (max. 100 kHz), PTO (max. 200 kHz)
22
C12
Digital input/output signal configurable C12
23
C13
Digital input/output signal configurable C13
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US
29