Parameter
Value
Output switching capacity (XC ver-
sion above 60 °C)
On request
Lifetime (cycles)
Mechanical: 300 000;
Under load: 300 000 (24 V DC at 2 A), 200 000 (120 V
AC at 2 A), 100 000 (230 V AC at 3 A)
Spark suppression with inductive AC
load
Must be performed externally according to driven load
specifications
Demagnetization with inductive DC
load
A free-wheeling diode must be circuited in parallel to
the inductive load
Switching frequency
With resistive load
Max. 10 Hz
With inductive load
Max. 2 Hz
With lamp load
On request
Max. cable length
Shielded
1000 m
Unshielded
600 m
Technical data of the fast counter
The fast counter of the module does not work if the module is connected to a
–
FBP interface module
–
CS31 bus module
–
CANopen communication interface module
Parameter
Value
Used inputs
I0 / I1
Used outputs
None
Counting frequency
50 kHz max.
Detailed description
See
Ordering data
Part no.
Description
Product life cycle phase *)
1SAP 245 200 R0001 DX522, digital input/output module,
8 DI, 24 V DC, 8 DO relays
Active
1SAP 445 200 R0001 DX522-XC, digital input/output
module, 8 DI, 24 V DC, 8 DO relays,
XC version
Active
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US