Name
Value
Internal
value
Internal
value,
type
Default
Min.
Max.
EDS Slot/
Index
Input
delay
0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
Byte
8 ms
0x02
0
3
0x0Y04
Fast
counter
4
)
0
:
10
3
)
0
:
10
Byte
Mode 0
0x00
Not for
FBP
Short cir-
cuit detec-
tion of
output or
sensor
supply
Off
On
0
1
Byte
On
0x01
0
1
0x0Y05
Behaviour
of outputs
at com-
munica-
tion errors
Off
Last value
Substitute
value
0
1+(n*5)
2+(n*5),
n
£
2
Byte
Off
0x00
0
2
0x0Y06
Substitute
value at
outputs
B23 =
Output 23
Bit 0 =
Output 0
0...
16777215
0...
0x00ff-ffff
DWord
0
0x0000
-0000
0
224−1
0x0Y07
Remarks:
1
)
With CS31 and addresses smaller than 70 and FBP, the value is increased
by 1
2
)
Not with FBP
3
)
For a description of the counter operating modes, please refer to the 'Fast
Counter' section
Chapter 1.6.1.2.9 “Fast counter” on page 349
4
)
With FBP or CS31 without the parameter Fast Counter
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
11
0x04, 0xc0, 0x08, \
0x01, 0x02, 0x01, 0x00, 0x00, 0x00, 0x00,
0x00;
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
285