Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Process supply voltage UP
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP)
as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
Rated value
24 V DC
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse on UP
10 A fast
Galvanic isolation
Yes, per module
Current consumption
From 24 V DC power supply at the ter-
minals UP/L+ and ZP/M of the CPU/com-
munication interface module
Ca. 2 mA
From UP at normal operation / with out-
puts
0.10 A + max. 0.5 A per output
Inrush current from UP (at power up)
0.005 A
2
s
Max. power dissipation within the module
6 W (outputs unloaded)
Weight (without terminal unit)
Ca. 100 g
Mounting position
Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
316