Channel parameters for the analog outputs (2x)
Name
Value
Internal value
Internal value,
type
Default
Output 0,
Channel configu-
ration
Operation modes
of analog outputs
Operation modes
of analog outputs
BYTE
0
Output 0, Check
channel
Channel moni-
toring
Channel moni-
toring
BYTE
0
Output 0, Substi-
tute value
Substitute value
Substitute value
WORD
0
Output 1,
Channel configu-
ration
Operation modes
of analog outputs
Operation modes
of analog outputs
BYTE
0
Output 1, Check
channel
Channel moni-
toring
Channel moni-
toring
BYTE
0
Output 1, Substi-
tute value
Substitute value
Substitute value
WORD
0
Table 139: Channel configuration - Operating modes of the analog outputs
Internal value
Operating Modes (individually configu-
rable)
0 (default)
Not used
128
-10 V...+10 V
129
0...20 mA
130
4...20 mA
Table 140: Channel monitoring
Internal value
Check channel
0
Plausib(ility), cut wire, short circuit
3
None
Table 141: Substitute value
Intended Behavior of Output
Channel when the Control
System Stops
Required Setting of
the Module Parameter
"Behavior of Outputs in
Case of a Communication
Error"
Required Setting of the
Channel Parameter "Substi-
tute value"
Output OFF
Off
0
Last value infinite
Last value
0
Last value for 5 s and then
turn off
Last value 5 sec
0
Last value for 10 s and then
turn off
Last value 10 sec
0
Substitute value infinite
Substitute value
Depending on configuration
Device specifications
Communication interface modules (S500) > CANopen
2022/01/31
3ADR010278, 3, en_US
643