Technical data of the digital inputs/outputs if used as inputs
Parameter
Value
Number of channels per module
Max. 16 digital inputs
Reference potential for all inputs
Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole of
the process supply voltage, signal name ZP)
Input current, per channel
See Technical Data of the Digital Inputs
Chapter 1.6.1.2.3.8.1 “Technical data of the
Input type acc. to EN 61131-2
Type 1
Input delay (0->1 or 1->0)
Typ. 8 ms, configurable from 0.1 to 32 ms
Input signal voltage
24 V DC
Signal 0
-3 V...+5 V *)
undefined signal
> +5 V...< +15 V
Signal 1
+15 V...+30 V
Ripple with signal 0
Within -3 V...+5 V *)
Ripple with signal 1
15 V...+30 V
Max. cable length
Shielded
1000 m
Unshielded
600 m
*) Due to the direct connection to the output, the demagnetizing varistor is also effective at the
input (see figure) above. This is why the difference between UPx and the input signal must not
exceed the clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V.
Consequently, the input voltage must range from -12 V to +30 V when UPx = 24 V and from
-6 V to +30 V when UPx = 30 V.
Technical data of the digital inputs/outputs if used as outputs
Parameter
Value
Number of channels per module
Max. 16 transistor outputs
Reference potential for all outputs
Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole
of the process supply voltage, signal name ZP)
Common power supply voltage
For all outputs: terminals 1.8, 2.8, 3.8 and 4.8
(positive pole of the process supply voltage,
signal name UP)
Output voltage for signal 1
UP (-0.8 V)
Output delay (0->1 or 1->0)
On request
Output current
Rated value, per channel
500 mA at UP = 24 V
Maximum value (all channels together)
8 A
Leakage current with signal 0
< 0.5 mA
Rated protection fuse on UP
10 A fast
Demagnetization when inductive loads are
switched off
With varistors integrated in the module (see
figure below)
Switching frequency
With resistive load
On request
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
300