Name
Value
Internal
Value
Internal
value,
Type
Default
Min.
Max.
EDS Slot
Index
Module ID Internal
6520
1
)
WORD
0x1978
0
65535
xx01
Ignore
module
No
Yes
0
1
BYTE
No
0x00
Parameter
length
Internal
8
BYTE
0
0
255
xx02
2
)
Check
Supply
Off
On
0 1
BYTE
On
0x01
Analog
Data
Format
Default
0
BYTE
Default
0x00
1
) With CS31 and addresses less than 70, the value is increased by 1
2
) Value is hexadecimal: HighByte is slot (xx: 0...7), LowByte is index (1...n)
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
0x0B
0x79, 0x19, 0x08, \
0x01, 0x00, \
0x00, 0x00, 0x00, 0x00, \
0x00, 0x00;
Input channel (4x)
Name
Value
Internal
value
Internal
value, Type
Default
Min.
Max.
Channel
configura-
tion
see table
2
) see table
2
) BYTE
0
0x00 see
table
2
)
0
65535
Table 79: Channel configuration
2
)
Internal value
Operating modes for the analog inputs, individually configu-
rable
0
Not used (default)
1
0 V...+10 V
3
0 mA...20 mA
4
4 mA...20 mA
6
0 V...+5 V
7
-5 V...+5 V
20
-2.5 V...+2.5 V
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
399