Range
-80 mV ... +80
mV
Type E
-270 ... +1000
°C
Types R, S
-50 ... +1768
°C
Digital value
Decimal
Hex.
-80 mV
-27648
9400
Underflow
< -90 mV
< -270.0 °C
< -50.0 °C
-32768
8000
Technical data
The System Data of AC500-eCo apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Parameter
Value
Process supply voltage UP
Connections
Terminal 19 for UP (+24 V DC) and terminal 20
for ZP (0 V)
Rated value
24 V DC
Current consumption
0.10 A
Inrush current (at power-up)
0.07 A
²
s
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse for UP
Not necessary
Current consumption from 24 V DC power
supply at the terminals UP/L+ and ZP/M of
the CPU/communication interface module
Ca. 5 mA
Galvanic isolation
Yes, between the channels and the rest of the
module
Isolated groups
1 (4 channels per group)
Surge-voltage (max.)
35 V DC for 0.5 s
Max. power dissipation within the module
2.6 W
Weight
Ca. 120 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
380