Parameter
Value
Vibration resistance
IEC 61131-2 / IEC 60068-26: 5 Hz...500 Hz, 2 g (with memory
card inserted)
IEC 60068-2-64: 5 Hz...500 Hz, 4 g rms
Shock resistance
IEC 60068-2-27: all 3 axes 15 g, 11 ms, half-sinusoidal
Table 210: EMC immunity
Parameter
Value
Electrostatic discharge (ESD)
Electrostatic voltage in case of air discharge: 8 kV
Electrostatic voltage in case of contact discharge: 6 kV
Fast transient interference vol-
tages (burst)
Supply voltage units (DC): 4 kV
Digital inputs/outputs (24 V DC): 2 kV
Analog inputs/outputs: 2 kV
Communication lines shielded: 2 kV
I/O supply (DC-out): 2 kV
High energy transient interference
voltages (surge)
Supply voltage units (DC): 1 kV CM *) / 0.5 kV DM *)
Digital inputs/outputs (24 V DC): 1 kV CM *) / 0.5 kV DM *)
Digital inputs/outputs (AC): 4 kV
Analog inputs/outputs: 1 kV CM *) / 0.5 kV DM *)
Communication lines shielded: 1 kV CM )*
I/O supply (DC-out): 0,5 kV CM *) / 0.5 kV DM *)
Influence of radiated disturbances Test field strength: 10 V/m
Influence of line-conducted inter-
ferences
Test voltage: 10 V
Power frequency magnetic fields
30 A/m 50 Hz
30 A/m 60 Hz
*) CM = Common Mode, * DM = Differential Mode
2.8 AC500-S
The AC500-S safety user manual must be read and understood before using safety configura-
tion and programming tools of Automation Builder / PS501 Control Builder Plus. Only qualified
personnel shall be allowed to work with AC500-S safety PLCs.
In order to have always the latest version and due to a different lifecycle compared to
Automation Builder help, the
is only available on our website.
The AC500-S safety PLC includes the following safety-relevant hardware components.
● SM560-S / SM560-S-FD-1 / SM560-S-FD-4
● DI581-S
● DX581-S
System assembly, construction and connection
AC500-S
2022/01/31
3ADR010278, 3, en_US
1027