Parameter
Value
Unused inputs
Must be configured as "unused".
Overvoltage protection
Yes
Technical data of the analog inputs, if used as digital inputs
Parameter
Value
Number of channels per module
Max. 8
Distribution of channels into groups
1 group of 8 channels
Connections of the channels C0+ to C7+
Terminals 3.0 to 3.7
Reference potential for the inputs
Terminals 1.9 to 4.9 (ZP)
Input signal delay
Typ. 8 ms, configurable from 0.1 to 32 ms
Indication of the input signals
1 LED per channel
Input signal voltage
24 VDC
Signal 0
-30 V...+5 V
Undefined signal
+5 V...+13 V
Signal 1
+13 V...+30 V
Input current per channel
Input v24 V
Typ. 7 mA
Input v5 V
Typ. 1.4 mA
Input v15 V
Typ. 4.3 mA
Input v30 V
< 9 mA
Input resistance
Ca. 3.5 k
W
Technical data of the analog outputs
Parameter
Value
Number of channels per module
8, all channels for voltage, the first 4 channels
also for current
Distribution of channels into groups
1 group of 8 channels
Channels C0-...C7-
Terminals 2.0...2.7
Channels C0+...C7+
Terminals 3.0...3.7
Output type
Bipolar with voltage, unipolar with current
Galvanic isolation
Against internal supply and other modules
Configurability
-10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually),
current outputs only channels 0...3
Output resistance (load), as current output
0
W
...500
W
Output loadability, as voltage output
Max.
±
10 mA
Indication of the output signals
One LED per channel
Resolution
12 bits (+ sign)
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US