Parameter
Value
Output current limitation
No
Resistance to feedback against 24 V DC
No
Connection of 2 outputs in parallel
Not possible
Max. cable length *)
Shielded
On request
Unshielded
On request
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Table 16: PM5032-T-ETH, PM5072-T-2ETH and PM5072-T-2ETHW
Parameter
Value
Number of channels per module
8
Distribution of the channels into groups
1 group of 8 channels
Galvanic isolation
Yes, per group
Connection of the channels O0 to O7
Terminals 14 to 21
Common power supply voltage
Terminals 24 (+24 V DC, signal name UP)
Reference potential for the channels O0 to O7
Terminal 25 (0 V DC, negative pole of the
process voltage, signal name ZP)
Indication of the output signals
1 yellow LED per channel; the LED is on
when the output signal is high (signal 1)
Way of operation
Non-latching type
Min. output voltage at signal 1
UP - 0.1 V
Output delay (max. at rated load)
0 to 1
On request
1 to 0
On request
Rated protection fuse (per group)
On request
Output current
Rated current per channel (max.)
0.5 A at UP 24 V DC (resistance, general
use and pilot duty)
Rated current per group (max.)
4 A
Rated current (all channels together, max.)
4 A
Max. leakage current with signal 0
0.5 mA
Demagnetization when inductive loads are
switched off
Must be performed externally according to
driven load specification
Switching Frequencies
With inductive loads
On request
Short-circuit-proof / Overload-proof
No
Overload message
No
Output current limitation
No
Resistance to feedback against 24 V DC
No
Connection of 2 outputs in parallel
Not possible
Max. cable length *)
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US
39