Parameter
Value
Reference potential for all inputs
Terminals 1.9...3.9 (Negative pole of the supply
voltage, signal name ZP)
Indication of the input signals
1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)
Input type (according EN 61131-2)
Type 1
Input delay (0->1 or 1->0)
Typ. 0.1 ms, configurable from 0.1...32 ms
Input signal voltage
24 V DC
Signal 0
-3 V...+5 V
Undefined Signal
> +5 V...< +15 V
Signal 1
+15 V...+30 V
Ripple with signal 0
Within -3 V...+5 V
Ripple with signal 1
15 V...+30 V
Input current per channel
Input v24 V
Typ. 5 mA
Input v5 V
> 1 mA
Input v15 V
> 2 mA
Input v30 V
< 8 mA
Max. cable length
Shielded
1000 m
Unshielded
600 m
Technical data of the digital outputs
Parameter
Value
Number of channels per module
8
Distribution of the channels into groups
1 group of 8 channels
Terminals of the channels DO0 to DO7
Terminals 3.0 to 3.7
Reference potential for all outputs
Terminals 1.9...3.9 (negative pole of the supply
voltage, signal name ZP)
Common power supply voltage
For all outputs terminal 3.8 (positive pole of the
supply voltage, signal name UP3)
Output voltage for signal 1
UP3 (-0.8 V)
Output delay (0->1 or 1->0)
On request
Output current
Rated value per channel
500 mA at UP3 = 24 V
Max. value (all channels together)
4 A
Leakage current with signal 0
< 0.5 mA
Fuse for UP3
10 A fast
Demagnetization with inductive DC load
Via internal varistors (see figure below this
table)
Output switching frequency
With resistive load
On request
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
857