Internal value
Operating modes of the analog inputs, individually configurable
16
2-wire Pt1000 -50...+400 °C
17
3-wire Pt1000 -50...+400 °C *)
18
2-wire Ni1000 -50...+150 °C
19
3-wire Ni1000 -50...+150 °C *)
*) In the operating modes with 3-wire configuration or with differential inputs,
two adjacent analog inputs belong together (e.g. the channels 0 and 1). In
these cases, both channels are configured in the desired operating mode.
The lower address must be the even address (channel 0). The next higher
address must be the odd address (channel 1). The converted analog value is
available at the higher address (channel 1).
Table 146: Channel monitoring
2
)
Internal Value
Check channel
0
Plausib(ility), cut wire, short circuit
3
not used
Channel parameters for the analog outputs (2x)
Name
Value
Internal value
Internal value,
type
Default
Output 0,
channel configu-
ration
see
3
)
see
3
)
BYTE
0
Output 0, check
channel
see
4
)
see
4
)
BYTE
0
Output 0, substi-
tute value
see
5
)
see
5
)
WORD
0
Output 1,
channel configu-
ration
see
3
)
see
3
)
BYTE
0
Output 1, check
channel
see
4
)
see
4
)
BYTE
0
Output 1, substi-
tute value
see
5
)
see
5
)
WORD
0
Table 147: Channel configuration
3
)
Internal value
Operating modes of the analog outputs, individually configu-
rable
0
Not used (default)
128
-10 V...+10 V
129
0...20 mA
130
4...20 mA
Device specifications
Communication interface modules (S500) > EtherCAT
2022/01/31
3ADR010278, 3, en_US
698