Effective January 2011
2C15991H02
08/10 AWA1230-2455
Ronis key interlock
IZM-KLP-SO-RONIS
warning
(1) Only qualified electrical persOnnel shOuld
be permitted tO wOrk On the equipment.
(2) always de-energize primary and
secOndary circuits if a circuit breaker
cannOt be remOved tO a safe wOrk lOcatiOn.
(3) drawOut circuit breakers shOuld be
levered (racked) Out tO the discOnnect
pOsitiOn.
(4) all circuit breakers shOuld be switched
tO the Off pOsitiOn and mechanism springs
discharged.
failure tO fOllOw these steps fOr all
prOcedures described in this instructiOn
leaflet cOuld result in death, bOdily injury,
Or prOperty damage.
warning
the instructiOns cOntained in this awa and On
prOduct labels have tO be fOllOwed. Observe
the five safety rules:
– discOnnecting
– ensure that devices cannOt be
accidentally restarted
– verify isOlatiOn frOm the supply
– earthing and shOrt-circuiting
– cOvering Or prOviding barriers tO
adjacent live parts
discOnnect the equipment frOm the supply.
use Only authOrized spare parts in the repair
Of the equipment. the specified maintenance
intervals as well as the instructiOns fOr
repair and exchange must be strictly adhered
tO prevent injury tO persOnnel and damage tO
the switchbOard.
Section 1: General information
This key interlock provides the following safety
features:
•
With no key, the breaker is OPEN and
cannot close
•
With the key ON (in cylinder) and rotated,
the breaker is fully functional
•
The key cannot be removed when the
breaker is ON (closed). The key cannot turn
the breaker OFF
Note:
N
To remove the key, press the breaker OFF button,
and rotate the key 90 degrees counterclockwise.
Rtquirtd oNNls
•
1/4-inch drive socket
•
10 mm socket
•
#2 Phillips head screwdriver
•
Adjustable crescent wrench
•
Needle nose pliers
•
3 mm wrench
•
Small blade screwdriver