16-14
IM 765601-01E
16.2.3 Sweep Commands (SWEep Group)
[:CHANnel<n>]:SWEep:TRIGger/?
Function Sets the sweep start (external, auxiliary trigger,
Timer1, Timer2, or measurement end) or queries
the current setting.
Syntax
[:CHANnel<n>]:SWEep:TRIGger
EXTernal|AUXiliary|TIMer1|TIMer2|
SENSe
EXTernal
Selects external start.
AUXiliary
Selects auxiliary trigger.
TIMer1
Selects Timer1 (constant period).
TIMer2
Selects Timer2 (constant period).
SENSe
Selects measurement end.
[:CHANnel<n>]:SWEep:TRIGger?
→ EXT
Set to external start.
→ AUX
Set to auxiliary trigger.
→ TIM1
Set to Timer1.
→ TIM2
Set to Timer2.
→ SENS
Set to measurement end.
Example
:SWE:TRIG EXT
:CHAN2:SWE:TRIG TIM1
:CHAN1:SWE:TRIG?
[:CHANnel<n>]:SWEep:TRIGger:
AUXiliary:POLarity/?
Function Sets the auxiliary trigger polarity (normal or
inverted) or queries the current setting.
Syntax
[:CHANnel<n>]:SWEep:TRIGger:
AUXiliary:POLarity NORMal|INVerted
NORMal
Selects normal (falling edge).
INVerted
Selects inverted (rising edge).
[:CHANnel<n>]:SWEep:TRIGger:
AUXiliary:POLarity?
→ NORM Set to normal (falling edge).
→ INV
Set to inverted (rising edge).
Example
:SWE:TRIG:AUX:POL NORM
:CHAN2:SWE:TRIG:AUX:POL INV
:CHAN1:SWE:TRIG:AUX:POL?
16.2 Commands
[:CHANnel<n>]:SWEep:COUNt/?
Function Sets the sweep repeat count or queries current
setting.
Syntax
[:CHANnel<n>]:SWEep:COUNt
<integer>|INFinity|MINimum|MAXimum
<integer>
Specify any repeat count.
INFinity
Sets the count to infinity.
MINimum Sets the count to minimum (= 1).
MAXimum Sets the count to maximum (= 1000).
[:CHANnel<n>]:SWEep:COUNt?
→ <integer> Current repeat count
→ INF
Set to infinity.
Example
:SWE:COUN 5
:CHAN2:SWE:COUN INF
:CHAN1:SWE:COUN?