en
Installation of CIF module
144
WILO SE 2022-05
Fig. 28:
Electronic module
The graphic display can be turned in 90° steps. To do this, open the upper part of the
electronic module using a screwdriver.
The graphic display is fixed in position by two snap-in hooks.
1.
Carefully open the snap-in hooks with a tool (e.g. screwdriver).
2.
Turn the graphic display to the desired position.
3.
Fix the graphic display with the snap-in hooks.
4.
Fit the upper part of the module again. Observe the screw tightening torques on
the electronic module.
Component
Fig./Item screw
(nut)
Thread
Tightening
torque
[Nm] ±10 %
(unless other-
wise stated)
Installa-
tion in-
formation
Electronic module
upper part
Fig. 28, Item 1
Fig. I, Item 2
M5
4.5
Threaded cable
gland union nut
Fig. 19, Item 1
M25
11
*
Threaded cable
gland
Fig. 19, Item 1
M25x1.5
8
*
Threaded cable
gland union nut
Fig. 19, Item 6
M20x1.5
6
*
Threaded cable
gland
Fig. 19, Item 6
M20x1.5
5
Power terminals and
control terminals
Fig. 20, 21
Pusher
Slot 0.6x3.5
**
Earthing screw
Fig. 20, Item 5
M5
4.5
CIF module
Fig. 28, Item 4
PT 30x10
0.9
Wilo-Connectivity
Interface cover
Fig. 1, Item 8
M3x10
0.6
Table 14:
Tightening torques for electronic module
*
Tighten when installing the cables.
**
Press with screwdriver to plug and unplug the cable.
8
Installation of CIF module
DANGER
Risk of fatal electrical shock!
Immediate risk of fatal injury if live components are touched!
• Check whether all connections are voltage-free!
CIF modules (accessories) are used for communication between pumps and building
management systems. CIF modules are attached in the electronic module (Fig. 28,
Item 4).
ƒ
For twin-head pumps, only the main pump must be equipped with a CIF module.
ƒ
For pumps in Y-pipe applications in which the electronic modules are connected to
each other through the Wilo Net, only the main pump also requires a CIF module.
NOTICE
When using CIF module Ethernet, the use of the accessory “Connection M12 RJ45
CIF-Ethernet” is recommended.
Required for easy disconnection of the data cable connection via the SPEEDCON
socket outside of the electronic module when maintenance of the pump is required.
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......