Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
173
Main pump
Partner pump
States
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
4
Not act-
ive
On
OK; normal
operation
Not act-
ive
On
OK; normal
operation
Table 27:
Single mode
Combined mode
The control input DI1 is equipped in the factory with a converter bridge and the func-
tion “EXT. OFF” is active.
The control input of the main pump switches both twin-
head pump partners off. The control input of the partner pump only switches the
partner pump off.
If the main pump fails or the twin-head pump connection is discon-
nected, the control input of the partner pump is evaluated.
Main pump
Partner pump
States
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
1
Active
Off
OFF
Override
OFF (DI1)
Active
Off
OFF
Override
OFF (DI1)
2
Not act-
ive
On
OK; normal
operation
Active
Off
OFF
Override
OFF (DI1)
3
Active
Off
OFF
Override
OFF (DI1)
Not act-
ive
Off
OFF
Override
OFF (DI1)
4
Not act-
ive
On
OK; normal
operation
Not act-
ive
On
OK; normal
operation
Table 28:
Combined mode
NOTICE
In regular operation, it is preferable to switch the pump on or off via the DI input
with EXT. OFF instead of via the mains voltage!
NOTICE
The 24 V DC power supply is only available when the analogue input AI1 or AI2 has
been configured to a type of use and a signal type or when the digital input DI1 has
been configured.
12.5
Application and function of the
analogue inputs AI1 and AI2
Analogue inputs can be used for setpoint input or actual value input. The assignment of
the target and actual value specifications depends on the selected control mode.
Analogue input AI1 is used as actual value input (sensor value). Analogue input AI2 is
used as setpoint input.
Set control mode
Function of analogue in-
put AI1
Function of analogue in-
put AI2
Δp-v
Configured as actual value
input
ƒ
Type of use: Differen-
tial pressure sensor
Configurable:
ƒ
Signal type
ƒ
Sensor measurement
range
ƒ
Sensor position
Not configured
Can be used as a setpoint
input
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......