Communication interfaces: Setting and function
172
WILO SE 2022-05
Procedure with EXT. OFF for twin-head pumps
Control input
Control input function
Twin-head pump ext.
OFF function
Fig. 65:
Digital input menu
The function EXT. OFF always behaves as follows:
ƒ
EXT. OFF active: contact is open, pump is stopped (OFF).
ƒ
EXT. OFF inactive: contact is closed, pump runs in normal operation (ON).
The twin-head pump consists of two partners:
ƒ
Main pump: Twin-head pump partner
with
connected differential pressure sensor
ƒ
Partner pump: Twin-head pump partner
without
connected differential pressure
sensor
The configuration of the control inputs has no effect on EXT. OFF which can influence
the behaviour of the two twin-head pump partners.
The possible behaviours are described in the following tables.
System mode
Twin-head pump
ext. OFF function
System mode
Single mode
Combined mode
Fig. 66:
Selectable modes for ext. OFF with
twin-head pump
The control input DI1 is equipped in the factory with a converter bridge and the func-
tion “EXT. OFF” is active.
The control input on the
main pump switches both twin-head pump partners
.
The
control input of the partner pump
is ignored and has
no meaning
regardless of its
configuration. If the main pump fails or the twin-head pump connection is disconnec-
ted, the partner pump is also stopped.
Main pump
Partner pump
States
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
1
Active
Off
OFF
Override
OFF (DI1)
Active
Off
OFF
Override
OFF (DI1)
2
Not act-
ive
On
OK; normal
operation
Active
On
OK; normal
operation
3
Active
Off
OFF
Override
OFF (DI1)
Not act-
ive
Off
OFF
Override
OFF (DI1)
4
Not act-
ive
On
OK; normal
operation
Not act-
ive
On
OK; normal
operation
Table 26:
System mode
Single mode
The control input DI1 is equipped in the factory with a converter bridge and the func-
tion “EXT. OFF” is active.
Each of the two pumps is individually switched by its own
control input.
If the main pump fails or the twin-head pump connection is disconnec-
ted, the control input of the partner pump is evaluated.
Main pump
Partner pump
States
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
1
Active
Off
OFF
Override
OFF (DI1)
Active
Off
OFF
Override
OFF (DI1/2)
2
Not act-
ive
On
OK; normal
operation
Active
Off
OFF
Override
OFF (DI1/2)
3
Active
Off
OFF
Override
OFF (DI1)
Not act-
ive
On
OK; normal
operation
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......