![Wilo Yonos GIGA2.0-D Installation And Operating Instructions Manual Download Page 158](http://html1.mh-extra.com/html/wilo/yonos-giga2-0-d/yonos-giga2-0-d_installation-and-operating-instructions-manual_982893158.webp)
en
Control settings
158
WILO SE 2022-05
If an external setpoint source (analogue input AI2 or CIF module) is selected, the menu
item “Substitute setpoint” opens. A fixed setpoint can be specified here, which is used
for control in the event of a malfunction of the setpoint source (such as a cable break at
the analogue input or no communication to the CIF module).
After confirming the selected setpoint source, the “Control setting” menu opens again.
10.4
Emergency operation
In the event of a malfunction, such as failure of the required sensor, an “emergency op-
eration” can be defined.
Emergency operation
Pump OFF
Pump ON
Fig. 45:
Setting emergency operation
In the “Emergency operation” menu, you can choose between “Pump OFF” and “Pump
ON”. To do this, select the following in succession:
Universal
Display text
1.0
Settings
1.1
Control settings
1.1.7
Emergency operation
OFF
Pump OFF
ON
Pump ON
Control settings
Setpoint Δp-v
Emergency operation
Emergency operation speed
Fig. 46:
Setting the emergency operation
speed
If “Pump ON” is selected, the corresponding speed can be set in the “Emergency opera-
tion speed” submenu:
Emergency operation
speed
3800 /Min
Fig. 47:
Emergency operation speed
Universal
Display text
1.0
Settings
1.1
Control settings
1.1.8
3
Emergency operation speed
3
3
Menu item opens only when emergency operation is set to “ON”.
After confirming the emergency operation speed setpoint, the “Control setting” menu
opens again.
10.5
Switch off motor
Control settings
Setpoint n-c
Setpoint source
Pump ON/OFF
Fig. 48:
Control setting pump ON/OFF
The motor of the pump can be switched on and off in the “Settings” menu
. To do
this, select the following in succession:
Universal
Display text
1.0
Settings
1.1
Control settings
1.1.15
Pump ON/OFF
OFF
Switched off
ON
Switched on
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......