Faults, causes and remedies
196
WILO SE 2022-05
Code
Warning
Cause
Remedy
553
Electronic module is de-
fective.
Electronic module is
defective.
Replace electronic module.
Additional information about causes and remedy
The pump is running, but cannot provide full power under the circumstances.
Contact service.
555 /
557
Implausible sensor value
at analogue input AI1 or
AI2.
The configuration
and the present sig-
nal lead to an unus-
able sensor value.
Check configuration of the
input and connected
sensor.
Additional information about causes and remedy
Incorrect sensor values may lead to substitute operating modes
that ensure functioning of the pump without the required sensor value.
556 /
558
Cable break at analogue
input AI1 or AI2.
The configuration
and the present sig-
nal help identify the
cable break.
Check configuration of the
input and connected
sensor.
Additional information about causes and remedy:
Cable break detection may lead to substitute operating modes that ensure
functioning of the pump without the required external value.
560
Incomplete software
update.
The software update
was not completed.
Software update with new
software bundle is recom-
mended.
Additional information about causes and remedy:
Software update was not carried out; pump continues to operate with previ-
ous software version.
561 /
562
Analogue input voltage
overloaded (binary or
analogue).
Voltage analogue in-
put short-circuited or
too heavily loaded.
Check the cables and con-
sumers connected to the
analogue input power sup-
ply for short circuits.
Additional information about causes and remedy:
Binary inputs are impaired. Functions of binary inputs are not available.
564
BMS
1)
setpoint is miss-
ing.
Sensor source or
BMS
1)
is configured
incorrectly.
Communication has
failed.
Check configuration and
function of BMS
1)
.
Additional information about causes and remedy:
Control functions impaired. A replacement function is active.
565 /
566
Signal too strong at
analogue input AI1 or
AI2.
The available signal is
significantly over the
expected maximum.
Check input signal.
Additional information about causes and remedy:
The signal is processed with the maximum value.
570
Electronic module too
hot.
Critical temperature
of the electronic
module exceeded.
Ensure permissible ambi-
ent temperature. Improve
room ventilation.
Additional information about causes and remedies:
The electronic module must adjust the pump’s operation in the event of no-
ticeable overheating
to prevent damage to electronic components.
571
Twin-head pump con-
nection interrupted.
The connection to
the twin-head pump
partner cannot be
made.
Check power supply of the
twin-head pump partner,
cable connection and con-
figuration.
Additional information about causes and remedy:
Pump function slightly impaired. The motor head meets the pump function
up to the performance limit.
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......