Installation
en
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
129
Component
Fig./
Item screw
(nut)
Thread
Tightening
torque
[Nm] ±10 %
(unless other-
wise stated)
Installation in-
formation
Capillary tube
screw connec-
tion to the
pump housing
0°
Fig. I, Item 5
R ⅛" brass
Hand-tight
Installation with
WEICONLOCK
AN 305‑11
Capillary tube
screw connec-
tion, union nut
90°
Fig. I, Item 6
M8x1
brass,
nickel-
plated
10
Only nickel-plated
nut (CV)
Capillary tube
screw connec-
tion, union nut
0°
Fig. I, Item 6
M6x0.75
brass,
nickel-
plated
4
Only nickel-plated
nut (CV)
Capillary tube
fitting, union
nut on differ-
ential pressure
sensor
Fig. I, Item 9
M6x0.75
brass
bright
2.4
Only bright brass
nuts
Motor adapter
for electronic
module
Fig. I, Item 4
M6
9
Table 6:
Screws and tightening torques
6.5
Preparing the installation
DANGER
Risk of fatal injury from falling parts!
The pump itself and pump parts can be extremely heavy. Falling parts pose a risk of
cuts, crush injuries, bruises or impacts, which can be fatal.
• Always use suitable lifting equipment and secure parts against falling.
• Never stand underneath a suspended load.
• During storage and transport, as well as before all installation and assembly work,
ensure that the pump is in a safe position and standing securely.
WARNING
Risk of personal injury and property damage due to improper handling!
• Never set up the pump unit on unfortified surfaces or surfaces that cannot bear
loads.
• Flush the pipe system if required. Dirt can cause the pump to fail.
• Install only after completion of all welding and soldering work and after the pipe
system has been flushed, if required.
• Observe the minimum axial distance of 400 mm between a wall and the fan cover
of the motor.
• Ensure free air access to the heat sink of the electronic module.
ƒ
The pumps must be protected from the weather and installed in a frost/dust-free,
well-ventilated environment that is not potentially explosive. Observe the instruc-
tions in “Intended use” [
114] section!
ƒ
Mount the pump in a readily accessible place. This makes it easier to complete in-
spections, maintenance (e.g. mechanical seal change) or replacement in the future.
ƒ
Install a device for attaching hoisting gear above the set-up site of large pumps.
Total weight of the pump: see catalogue or data sheet.
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......