Maintenance
en
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
205
4.
Press the electronic module into the new motor contacting and fasten with screws
(Fig. I, Item 4).
Restore the pump’s operational readiness: see section “Replacing the mechanical seal”
[
200]; steps 5 ... 1!
NOTICE
The electronic module must be pressed on as far as possible when it is installed.
NOTICE
Disconnect the electronic module from the mains supply when performing another
insulation test on site!
18.2.4
Module fan replacement
To dismantle the module, see section “Replacing the electronic module” and steps
1 ... 5 in the section “Replacing the mechanical seal” [
Dismantling the fan
Fig. 102:
Open the cover of the electronic
module
1.
Open the cover of the electronic module.
Fig. 103:
Loosen the connection cable of the
module fan
2.
Remove the connection cable of the module fan.