Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
171
SSM/SBM relay
Forced control
Help text
Forced active
SSM/SBM relay switching status is forced ACTIVE.
CAUTION:
SSM/SBM does not display the pump status!
Forced inactive
SSM/SBM relay switching status is forced INACT-
IVE.
CAUTION:
SSM/SBM does not display the pump status!
Table 24:
Selection option SSM/SBM relay forced control
The “Forced active” setting permanently activates the relay. This means that, for ex-
ample, a warning/operating note (light) is permanently displayed/announced.
The “Forced inactive” setting leaves the relay permanently without a signal. No warn-
ing/operating note can be confirmed.
12.4
Application and function of the
digital control input DI1
The pump can be switched on or off via external potential-free contacts at the digital
input.
The following table provides an overview of the “Control input” menu:
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.2
Control input
1.3.2.1
Control input function
1.3.2.1 / 1
Not used
1.3.2.1 / 2
External OFF
1.3.2.2
1
Twin-head Pump ext. OFF function
1
1.3.2.2 / 1
System mode
1.3.2.2 / 2
Single mode
1.3.2.2 / 3
Combined mode
1
The submenu only opens when the twin-head pump is connected
Possible settings:
Control input function
Not used
External OFF
Fig. 64:
Digital input menu function
Selection option
Digital input function
Not used
The control input does not have a function.
External OFF
Contact open:
Pump is switched off.
Factory setting:
Contact closed:
Pump is switched on.
Table 25:
Control input function DI1
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......