en
Double pump operation
162
WILO SE 2022-05
Menu “Connecting twin-head pump”
Dual pump management
Connecting twin-head pump
Pump housing type
Fig. 51:
Dual pump management menu
If a twin-head pump connection has not yet been established, select the following in
the “Settings” menu
:
Universal
Display text
1.0
Settings
1.4
Dual pump management
1.4.1
Connecting twin-head pump
Connecting twin-head pump
Twin-head pump partner
address
Establish twin-head pump
connection
Fig. 52:
Connect twin-head pump menu
The Wilo Net address of the twin-head pump partner must first be set for both pumps
of the twin-head pump.
Example:
Pump I is assigned the Wilo Net address 1, pump II the Wilo Net address 2.
The address 2 of the twin-head pump partner must then be set in pump I and address 1
in pump II.
Connecting twin-head pump
Twin-head pump partner
address
Establish twin-head pump
connection
Twin-head pump
partner address
NOTICE
180] and “Connection of Wilo Net for twin-head pump func-
143].
When the configuration of the partner addresses is complete, the twin-head pump
connection can be started or cancelled.
Universal
Display text
1.4.1
Connecting twin-head pump
1.4.1.1
Twin-head pump partner address
1.4.1.2
Establish twin-head pump connection
NOTICE
The pump from which the twin-head pump connection is started is the main pump.
Always select the pump to which the differential pressure sensor is connected as the
main pump.
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......