Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
175
Analogue input (AI1)
Signal type
Pressure sensor range
Pressure sensor position
Fig. 67:
Analogue input AI1 menu
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.3
Analogue input (AI1)
1.3.3.1
Signal type
Possible signal types when selecting the analogue input as actual value input:
Signal type (AI1)
Fig. 68:
Signal types menu
Actual value sensor signal types:
0 ... 10 V:
Voltage range from 0 ... 10 V for the transmission of measured values.
2 ... 10 V:
voltage range of 2 ... 10 V for the transfer of measurement values. A cable
break is detected at a voltage below 1 V.
0 ... 20 mA:
Electric current range from 0 ... 20 mA for the transmission of measured
values.
4 ... 20 mA:
electric current range of 4 ... 20 mA for transfer of measured values. A cable
break is detected if the electric current is less than 2 mA.
For the transfer of analogue signal values to actual values, only the transfer ramp is now
defined. The transmission characteristics are fixed and are as follows:
Signal type 2 ... 10 V / 4 ... 20 mA
Factory setting:
The analogue input AI1 is factory-set with the differential pressure sensor (with variant
R1: not assigned) and set to signal type 2 ... 10 V.
Pressure sensor range (AI1)
16.0 bar
Fig. 69:
Setting the pressure sensor range
“Pump flange” is set as the pressure sensor position.
The pressure value set in the factory as the pressure sensor range (see Fig. 67 Analogue
input AI1 menu and Fig. 69 Pressure sensor range AI1) corresponds to the maximum
sensor range of the connected differential pressure sensor.
The pressure sensor range varies depending on the pump type.
The sensor range is documented on the rating plate of the differential pressure sensor.
Universal
Display text
1.3.3
Analogue input (AI1)
1.3.3.1
Signal type
1.3.3.2
Pressure sensor range
1.3.3.3
Pressure sensor position
1.3.3.3 / 1
Pump flange
1.3.3.3 / 2
Standard-compliant position
The actual value of the differential pressure runs linearly between the analogue signals
2 V and 10 V. This corresponds to 0 % ... 100 % of the sensor measuring range. (See
diagram Fig. 70).
6HQVRU
>@
9
P$
9
P$
9
P$
)DOOEDFN
Fig. 70:
Behaviour of analogue input AI 1: Sensor value with signal type 2 ... 10 V /
4 ... 20
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......