RLC-SVX07A-EN
53
Installation - Remote Condenser
Table 11
Maximum Allowable Liquid Line Drainable to the Evaporator
(Actual Ft.)
CIRCUIT SIZE Liquid
Line Size (O.D.)
30 Ton
40 Ton
50 Ton
60 Ton
1 1/8
200
200
200
200
1 3/8
125
125
175
200
Table 12
Horizontal or Downflow Discharge Line Sizes (O.D.)
35 Ton Circuit
40 Ton Circuit
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
40 - 60 F
20 - 39 F
0 - 19 F
40 - 60 F
20 - 39 F
0 - 19 F
25
2 1/8
1 5/8
1 5/8
25
2 1/8
1 5/8
1 5/8
50
2 1/8
1 5/8
1 5/8
50
2 1/8
1 5/8
1 5/8
75
2 1/8
1 5/8
1 5/8
75
2 1/8
1 5/8
1 5/8
100
2 1/8
1 5/8
1 5/8
100
2 1/8
1 5/8
1 5/8
125
2 1/8
1 5/8
1 5/8
125
2 1/8
1 5/8
1 5/8
150
2 1/8
1 5/8
1 5/8
150
2 1/8
1 5/8
1 5/8
175
2 1/8
1 5/8
1 5/8
175
2 1 /8
1 5/8
1 5/8
200
2 1/8
1 5/8
1 5/8
200
2 1/8
1 5/8
1 5/8
225
2 1/8
2 1/8
1 5/8
225
2 1/8
2 1/8
1 5/8
250
2 1/8
2 1/8
1 5/8
250
2 1/8
2 1/8
1 5/8
275
2 1/8
2 1/8
1 5/8
275
2 1/8
2 1/8
1 5/8
300
2 1/8
2 1/8
1 5/8
300
2 1/8
2 1/8
1 5/8
50 Ton Circuit
60 Ton Circuit
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
Total
Equiv.
Length
(ft.)
Leaving Evaporator Water Temperature (F)
40 - 60 F
20 - 39 F
0 - 19 F
40 - 60 F
20 - 39 F
0 - 19 F
25
2 1/8
2 1/8
2 1/8
25
2 1/8
2 1/8
2 1/8
50
2 1/8
2 1/8
2 1/8
50
2 1/8
2 1/8
2 1/8
75
2 1/8
2 1/8
2 1/8
75
2 1/8
2 1/8
2 1/8
100
2 1/8
2 1/8
2 1/8
100
2 1/8
2 1/8
2 1/8
125
2 1/8
2 1/8
2 1/8
125
2 1/8
2 1/8
2 1/8
150
2 1/8
2 1/8
2 1/8
150
2 1/8
2 1/8
2 1/8
175
2 1/8
2 1/8
2 1/8
175
2 5/8
2 1/8
2 1/8
200
2 1/8
2 1/8
2 1/8
200
2 5/8
2 1/8
2 1/8
225
2 5/8
2 1/8
2 1/8
225
2 5/8
2 1/8
2 1/8
250
2 5/8
2 1/8
2 1/8
250
2 5/8
2 1/8
2 1/8
275
2 5/8
2 1/8
2 1/8
275
2 5/8
2 1/8
2 1/8
300
2 5/8
2 1/8
2 1/8
300
2 5/8
2 1/8
2 1/8
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...