RLC-SVX07A-EN
41
Installation - Mechanical
Water Treatment
Using untreated or improperly treated water in these units may result in ineffi-
cient operation and possible tube damage. Consult a qualified water
treatment specialist to determine whether treatment is needed. The
following disclamatory label is provided on each RTWA and RTUA unit:
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in a Chiller may
result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment
specialist be engaged to determine what water treatment, if any,
is required. Trane assumes no responsibility for equipment
failures which result from untreated or improperly treated water,
or saline or brackish water.
Water Pressure Gauges
Install field-supplied pressure gauges (with manifolds, whenever practical) on
the RTWA and RTUA units, as shown in Figures
15
,
19
and
20
. Locate
pressure gauges or taps in a straight run of pipe; avoid placement near
elbows, etc. Be sure to install the gauges at the same elevation.
To read manifolded pressure gauges, open one valve and close the other
(depending upon the reading desired). This eliminates errors resulting from
differently calibrated gauges installed at unmatched elevations.
Water Pressure Relief Valves
Install a water pressure relief valve in the condenser and evaporator leaving
chilled water piping. See Figures
15
,
19
and
20
. Water vessels with close
coupled shutoff valves have a high potential for hydrostatic pressure buildup
on a water temperature increase. Refer to applicable codes for relief valve
installation guidelines.
CAUTION
Prevent Shell Damage!
To prevent shell damage, install pressure relief valves in both the
evaporator and condenser water systems.
Field-Installed Water Temperature Sensors
Entering and leaving evaporator water temperature sensors (6RT7, 6RT8) are
factory installed on all units, excluding the RTCA. Entering and leaving
condenser water temperature sensors are factory installed in the condenser
water boxes, if the “Condenser Water Temperature Sensor Kit” is ordered
with the unit (RTWA only).
Water Sensor Installation Procedure
If field installation is required, the sensors must be properly located to read a
mixed water temperature. An installed sensor and fitting is illustrated in
Figure
22
.
1.
Cut a properly-sized hole in the piping and weld a 1/4” NPT 150 psig half-
coupling (field-provided) into the piping at each sensor location.
2.
Using teflon tape, install the entire sensor compression fitting into the
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...