RLC-SVX07A-EN
67
Installation - Electrical
Low Voltage Wiring
The remote devices described below require low voltage wiring. All wiring to
and from these remote input devices to the UCM, as described below in
Paragraphs
"Emergency Stop (Normal Trip) on Page" 67
through
"Outdoor Air
Temperature Sensor on Page" 74
, are for RTWA and RTUA units only and
must be made with shielded, twisted-pair conductors. Be sure to ground the
shielding only at the Clear Language Display. Refer to the Section on
“Unit
Wiring”
for the recommended conductor sizes.
NOTE:
To prevent control malfunctions, do not run low voltage wiring (<30
V) in conduit with conductors carrying more than 30 volts.
Emergency Stop (Normal Trip)
The Clear Language Display provides auxiliary control for a customer
specified/installed latching trip out. When this customer-furnished remote
contact (5K18) is provided, the chiller will run normally when the contact is
closed. When the contact opens, the unit will trip off on a manually resettable
diagnostic. This condition requires manual reset at the chiller switch on the
front of the Clear Language Display.
To connect, first remove the jumper located between terminals 3 and 4 of
1U1TB1. Connect low voltage leads 513 and 514 to those terminals. Terminal
strip locations are shown in Section
“Unit Wiring”
. Refer to the field diagrams
which are shipped with the unit.
Silver or gold-plated contacts are recommended. These customer furnished
contacts must be compatible with 12 VDC, 45 mA resistive load.
External Circuit Lockout - Circuit #1
The UCM provides for auxiliary control via a customer specified or installed
contact closure, for individual operation of Circuit #1. If the contact is closed,
the refrigerant circuit will not operate. The refrigerant circuit will run normally
when the contact is opened. This feature is used to restrict total chiller
operation, eg. during emergency generator operations.
External circuit lockout will only function if External Circuit Lockout (Service
Setting Menu) is enabled.
These customer-supplied contact closures must be compatible with 12 VDC,
45 mA resistive load. Silver or gold plated contacts are recommended.
To install, cut, strip and wire-nut existing wire loop #W7 on the J3 connector
of the 1U4 module to low voltage leads 45A and 45B. Connections are shown
in the field diagrams which are shipped with the unit.
External Circuit Lockout - Circuit #2
The UCM provides for auxiliary control vai a customer specified or installed
contact closure, for individual operation of Circuit #2. If the contact is closed,
the refrigerant circuit will not operate. The refrigerant circuit will run normally
when the contact is opened. This feature is used to restrict total chiller
operation, eg. during emergency generator operations.
External circuit lockout will only function if External Circuit Lockout (Service
Setting Menu) is enabled.
These customer-supplied contact closures must be compatible with 12 VDC,
45 mA resistive load. Silver or gold plated contacts are recommended.
To install, cut, strip and wire-nut existing wire loop #W4 on the J3 connector
of the 1U5 module to low voltage leads 46A and 46B. Connections are shown
in Section
“Refrigerant Charging”
and in the field diagrams which are shipped
with the unit.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...