RLC-SVX07A-EN
55
Installation - Remote Condenser
NOTE:
Failure to properly mount and insulate the saturated condensing
refrigerant temperature sensor could cause poor control and/or possible
compressor damage.
If the sensor cannot be located at the point where the saturated gas enters
the subcooler, locate the sensor closer to the subcooler rather than the
condenser discharge gas. If saturated condensing temperature cannot be
measured, it is preferred to measure liquid temperature rather than discharge
temperature.
Refer to
"Interconnecting Wiring" on Page 62
for interconnecting wiring of
sensors for non-RTCA units.
NOTE:
The RTUA unit ships with the outdoor ambient sensor and two
saturated condenser temperature sensors in the control panel.
Refrigerant Charge Determination
The approximate amount of the refrigerant charge required by the system
must be determined by referring to Table
14
and must be verified by running
the system and checking the liquid line sightglasses.
To determine the approximate charge, first refer to Table
13
and establish the
required charge without the field-installed piping. Then refer to Table
14
, to
determine the charge required for the field-installed piping. The approximate
charge is therefore the sum of the values from Tables
14
and
15
.
Table 14
System Refrigerant Charge
Circuit Size
LBS of R-22
35
58
40
61
50
73
60
98
Table 15
Field-Installed Piping Charge
PIPE O.D
DISCHARGE LINE (LBS.)
LIQUID LINE (LBS.)
7/8
-----
24
1 1/8
-----
41
1 3/8
4
62
1 5/8
6
88
2 1/8
10
153
2 5/8
15
236
Note:
The amounts of refrigerant listed in Table
15
are based on 100 feet of pipe.
Actual requirements will be in direct proportion to the actual length of the
piping.
Note:
Table
14
assumes:
Liquid temperature = 100 F
Saturated Discharge Temp. = 125 F
Discharge Superheat = 55 F
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...