Controls Interface
Operational Features
Entering Evaporator Water Temperature
When one or both compressors are running, the UCM continually monitors
and compares the entering and leaving evaporator water temperatures. If the
temperature of the entering water drops more than 2 F below the leaving
water temperature for more than 100 degree F seconds, the UCM uses this
to indicate a loss of water flow through the evaporator. This will shut down
that circuit's compressor and will display an MMR diagnostic.
Current Limit Setpoint
The current limit setpoints for the system (front panel or remote) are entered
through the Clear Language Display menus. The current limit setpoint for
each compressor is shown in
Table 25
.
Based upon current levels received at the UCM, the compressor slide valve is
modulated to prevent the actual chiller current from exceeding the CLS.
When a compressor is turned off, the CLS for the remaining running
compressor shall be reset upward immediately. When a compressor is
added, the CLS for the running compressor shall be ramped downward at a
rate not less than 10% RLA per minute to the new setpoint.
Low Ambient Lockout
The lockout provides a method for preventing unit start-up when the outdoor
air temperature is below the setpoint. If the outdoor temperature goes below
the setpoint during operation, the UCM will go through a normal shutdown of
the unit. If the outdoor temperature subsequently increases to 5 F above the
setpoint, the UCM will automatically re-enable the unit. The low ambient
lockout feature has a range from -20 F to 60 F
Electronic Expansion Valve (EXV) Test
This test can be performed only when the Stop key has been pressed. It will
confirm proper operation of the electronic expansion valve and the EXV
module.
Once the test has been initiated at the Clear Language Display, the UCM will:
1.
Overdrive the EXV closed (25 seconds)
2.
Overdrive the EXV open (25 seconds)
3.
Overdrive the EXV closed (25 seconds)
4.
Reset the display to disable and end the test.
The EXV produces an audible clicking sound when it is driven against its end
stops. Step 1 drives the EXV to its closed position, during which time service
personnel can move from the Clear Language Display to the EXV.
NOTE:
A tool may be needed to aid in hearing the clicking of the EXV, such
as a screwdriver held between the EXV and the ear.
When Step 1 completes, the clicking stops and the UCM begins to open the
EXV. When the EXV is fully opened, the valve will begin to click against its end
stop. The service personnel must be prepared to time the period between
the end of clicking in Step 1 and the beginning of clicking in Step 2.
The time between the end of clicking in Step 2 and the beginning of clicking
in Step 3 must also be recorded. The time for the EXV to go from fully closed
to fully open (which is the first time recorded) should be approximately 15
seconds. The time to go back to fully closed (which is the second time
recorded) is approximately 15 seconds.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...