RLC-SVX07A-EN
79
Installation - Electrical
NOTE:
If an electrical box is to be used, attach it to the display box with
screws through the four mounting slots around the knockout.
The top of the display box is marked “TOP”. Note the position of the box
before mounting it to the surface. With the box in the desired position against
the mounting surface, mark the location of the mounting holes.
Remove the box and drill the necessary holes in the surface. Put the display
box back in position and secure it to the mounting surface with the required
screws.
The keypad board can now be swung back into position and secured.
Remote CLD Panel Wiring
The Remote CLD requires a 24-volt power source and a shielded, twisted-pair
wire between the panel and the Clear Language Display. See
Figure
34
.
As shown in
Figure
34
, the wire runs from terminals J3A-1(+) and J3A2(-) in
the unit's buffer module (1U7) to terminals (+) and (-) in the Remote CLD. Be
sure that one lead is connected to the (+) terminal at each end and the other
lead is connected to the (-) terminal at each end.
Do not run the shielded, twisted-pair wire in a conduit that also contains
circuits of greater than 30 volts. Attach the shield to a grounding lug in the
Remote CLD Panel. Cut and tape the shield at the Unit Control Panel, as
shown in
Figure
33
.
NOTE:
Shielding of the twisted pair can be grounded at either the Unit
Control Panel or the Remote CLD Panel as long as both sides are NOT
grounded.
Connect the 24-volt power supply to terminals J2-A and J2-B in the Remote
CLD panel. The polarity of the power source is not a concern, but the power
source must be grounded to terminal J2 GND.
NOTE:
A field-supplied Class 2, 24 VAC, 40 VA transformer can be used as a
power supply for the Remote CLD Panel.
NOTE:
Both a Remote CLD and a Tracer unit can be connected to the UCM.
ICS Address Setting
The setting if the ICS address for the Remote CLD is not necessary.
Multiple Unit Operation
In a multiple unit configuration, the Remote CLD panel has the capability to
communicate with up to four units. Each unit requires a separate communi-
cation link with the Remote CLD panel.
Figure 33
Shielded, Twisted Pair Communication LInk at the
Remote CLD Panel
7RAPTAPEAROUND
EXPOSEDFOILSHIELD
ANDBARESHIELDWIRE
#ONNECTLEADSTO
5NIT#ONTROL0ANEL
-AX
#UTBACKBARE
SHIELDWIRE
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...