73
Installation - Electrical
isolated or “floating” with respect to the UCM chassis ground. Refer to the
Section
“Unit Wiring”
.
If the potentiometer is to be remotely mounted, it and the resistor must be
connected to the UCM prior to mounting. Then, with the Clear Language
Display showing “Active Current Limit Setpoint” (Chiller Report Menu), the
Clear Language Display can be used to calibrate the positions of the potenti-
ometer to correspond with the desired settings for the current limits. External
resistor input values for various current limit setpoints are shown in
Table
28
.
4.
VDC Voltage Source Input
Set DIP Switch SW1-2 of Options Module 1U2 to “OFF”. Connect the voltage
source to terminals TB17 (+) and TB1-8 (-) of Options Module 1U2. CLS is
now based on the following equation:
CL Setpoint% = (VDC x 10) + 20
Sample values for CLS vs. VDC signals are shown in
Table
21
.
5.
4-20 mA Current Source Input
Set DIP Switch SW1-2 of Options Module 1U2 to “ON”. Connect the current
source to terminals T131-7 (+) and TB1-8 (-) of Options Module 1U2. CLS is
now based on the following equation:
CL Setpoint% _ (mA x 5) + 20
Sample values for CLS vs. mA signals are shown in
Table
22
.
NOTE:
The negative terminal TB1-8 is referenced to the UCM chassis
ground. To assure correct operation, 2-10 VDC or 4-20 mA signals must be
isolated or “floating” with respect to the UCM chassis ground. Refer to the
Section
“Unit Wiring”
.
Figure 31
Resistor and Potentiometer Arrangement for External Current
Limit Setpoint
Minimum setpoint = 40% (2.0 VDC input)
Maximum setpoint =
120% (10.0 VDC input)
Maximum continuous input voltage = 15 VDC
Input impedance (SW1-1 on)
(SW1-2 off)
= 40.1 Kohms
Minimum setpoint = 40% (0 mA)
Maximum setpoint = 120% (20.0 mA)
Maximum continuous input voltage = 30 mA
Input impedance
(SW1-2 on)
= 499 ohms
7%
0RGXOH8
7%
0RGXOH8
&&:
2KPVî:
.2KP/RJ&&:3RWHQWLRPHWHU
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...