124
RLC-SVX07A-EN
Pre-Start Checkout
Voltage to the unit must meet the criteria given in
Table
16
. Measure each leg
of the supply voltage at the unit's main power fused-disconnect. If the
measured voltage on any leg is not within specified range, notify the supplier
of the power and correct the situation before operating the unit.
CAUTION
Equipment Damage!
Inadequate voltage to the unit may cause control components to
malfunction and shorten the life of relay contact, compressor
motors and contactors.
Unit Voltage Imbalance
Excessive voltage imbalance between the phases of a three-phase system
can cause motors to overheat and eventually fail. The maximum allowable
imbalance is 2 percent. Voltage imbalance is determined using the following
calculations:
= phase with greatest difference from V
ave
(without regard to sign)
For example, if the three measured voltages are 221, 230, and 227 volts, the
average would be:
The percentage of imbalance is then:
This exceeds the maximum allowable (2%) by 0.2 percent.
Unit Voltage Phasing
It is important that proper rotation of the compressors be established before
the unit is started. Proper motor rotation requires confirmation of the
electrical phase sequence of the power supply. The motor is internally
connected for clockwise rotation with the incoming power supply phased A,
B, C.
Basically, voltages generated in each phase of a polyphase alternator or circuit
are called phase voltages. In a three-phase circuit, three sine wave voltages
are generated, differing in phase by 120 electrical degrees. The order in which
the three voltages of a three-phase system succeed one another is called
phase sequence or phase rotation. This is determined by the direction of
rotation of the alternator. When rotation is clockwise, phase sequence is
usually called “ABC”, when counterclockwise, “CBA”.
% Imbalance
l
x
l
ave
–
(
)
x 100
l
ave
-------------------------------------
=
V
ave
V
1
V
2
V
3
+
+
(
)
3
--------------------------------------
=
1V
x
221 230 227
+
+
3
---------------------------------------
226
=
100 221 226
–
(
)
226
--------------------------------------
2.2%
=
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...