![Trane R Series Installation Operation & Maintenance Download Page 31](http://html.mh-extra.com/html/trane/r-series/r-series_installation-operation-and-maintenance_1149684031.webp)
RLC-SVX07A-EN
31
Installation - Mechanical
Water Piping
Thoroughly flush all water piping to the RTWA/RTUA unit before making the
final piping connections to the unit.
CAUTION
Equipment Damage!
If using an acidic commercial flushing solution, construct a
temporary bypass around the unit to prevent damage to internal
components of the evaporator.
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in a Chiller may
result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment
specialist be engaged to determine what water treatment, if any,
is required. Trane assumes no responsibility for equipment
failures which result from untreated or improperly treated water,
or saline or brackish water.
CAUTION
Use Piping Strainers!
To prevent evaporator or condenser damage, pipe strainers must
be installed in the water supplies to protect components from
water born debris. Trane is not responsible for equipment-only-
damage caused by water born debris.
Evaporator Water Piping (for RTWA and RTUA Units Only)
Figure 15
illustrates typical evaporator piping components. Components and
layout will vary slightly, depending on the location of connections and the
water source.
CAUTION
Equipment Damage!
The chilled water connections to the evaporator are to be grooved
connections. Do not attempt to weld these connections, as the
heat generated from welding can cause internal damage to the
evaporator.
The chilled water connections are on the back of the unit, when facing the
control panel.
A vent is provided on the top of the evaporator at the return end. Be sure to
provide additional vents at high points in the piping to bleed air from the
chilled water system. Install necessary pressure gauges to monitor the
entering and leaving chilled water pressures.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...