Installation - Mechanical
Condenser Water Piping (for RTWA Units Only)
Condenser water inlet and outlet types, sizes and locations are given in
Figures
3
to Condenser pressure drops are shown in Figures
17
and
18
.
Condenser Piping Components
Condenser piping components and layout vary, depending on the location of
connections and the water source.
Figure 19
illustrates typical piping compo-
nents for a well water (or city water) condensing source. Typical components
for a cooling tower condensing source are shown in
Figure 20
.
Condenser piping components generally function identically to those in the
evaporator piping system, as described in
"Evaporator Water Piping (for
RTWA and RTUA Units Only)" on Page 31
. In addition, cooling tower systems
should include a manual or automatic bypass valve that can alter the water
flow rate, to maintain condensing pressure. Well water (or city water)
condensing systems should include a pressure reducing valve and a water
regulating valve, as shown in
Figure 19
.
The pressure reducing valve should be installed to reduce water pressure
entering the condenser. This is required only if the water pressure exceeds
150 psig. This is necessary to prevent damage to the disc and seat of the
water regulating valve that can be caused by excessive pressure drop through
the valve and also due to the design of the condenser. The condenser
waterside is rated at 150 psi.
CAUTION
Equipment Damage!
To prevent damage to the condenser or regulating valve, the
condenser water pressure should not exceed 150 psig.
The optional water regulating valve maintains condensing pressure and
temperature by throttling water flow leaving the condenser in response to
compressor discharge pressure. Adjust the regulating valve for proper
operation during unit start-up.
This valve is not used in cooling tower applications. Cooling towers, however,
may require the use of a three-way, pilot-operated regulating/bypass valve, to
maintain balance between cooling tower water temperature and condensing
pressure.
NOTE:
Plugged tees are installed to provide access for chemical cleaning of
the condenser tubes.
Condenser piping must be in accordance with all applicable local and national
codes.
Condenser Drains
The condenser shells can be drained by removing the drain plugs from the
bottom of the condenser heads. Also, remove the vent plugs at the top of the
condenser heads to facilitate complete drainage.
When the unit is shipped, the drain plugs are removed from the condenser
and placed in a plastic bag in the control panel, along with the evaporator
drain plug. The condenser drains may be connected to suitable drains to
permit drainage during unit servicing. If they are not, the drain plugs must
be installed.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...