152
RLC-SVX07A-EN
Diagnostics
Tracer Communications Loss
IFW
a.
While the chiller switch was in AUTO/REMOTE the
communications between the CSR and the connected
remote device, e.g., a Tracer or Remote Display, had
either never been established for more than 15 minutes
after power up or had been lost for more than 15
minutes after it had been established; use the Front
Panel Setpoints and the Default Chiller Auto/Stop.
b.
In AUTO/LOCAL communications had been established
and was then lost for more than 15 minutes. Regardless
of the remote communications status the UCM uses
Front Panel setpoints.
NOTE:
The active modes for this diagnostic follow
the positions of the chiller switch which account for
other chiller modes.
Under Voltage
MAR
Line voltage below - 10% of nominal or the Under/Over trans-
former is not connected. (Must hold = -10% of nominal. Must
trip = -15% of nominal. Reset differential = min. of 2% and
max. of 4%. Time to trip = min. of 10 sec. and max. of 20 sec.)
Design: Nom. trip: 15 seconds at less than 87.5%. ± 2.8% at
200V. or ± 1.8% at 575V, Auto reset at 90.5% or greater.
U1 Indicating U2 Communications
IFW
The 1U1 has det. a loss of IPC comm from the 1U2 module.
U1 Indicating U3 Communications
MMR
The 1U1 has det. a loss of IPC comm from the 1U3 module.
U1 Indicating U4 Communications
CMR
The 1U1 has det. a loss of IPC comm from the 1U4 module.
U1 Indicating U5 Communications
CMR
The 1U1 has det. a loss of IPC comm from the 1U5 module.
U1 Indicating U6 Communications
CMR
The 1U1 has det. a loss of IPC comm from the 1U6 module.
U1 Indicating U7 Communications
CMR
The 1U1 has det. a loss of IPC comm from the 1U7 module.
U3 Indicating U1 Communications
MMR
The 1U3 has det. a loss of IPC comm from the 1U1 module.
U3 Indicating U4 Communications
CMR
The 1U3 has det. a loss of IPC comm from the 1U4 module.
U3 Indicating U5 Communications
CMR
The 1U3 has det. a loss of IPC comm from the 1U5 module.
U3 Indicating U6 Communications
CMR
The 1U3 has det. a loss of IPC comm from the 1U6 module.
U3 Indicating U7 Communications
CMR
The 1U3 has det. a loss of IPC comm from the 1U7 module.
U4 Indicating U1 Communications
CMR
The 1U4 has det. a loss of IPC comm from the 1U1 module.
U4 Indicating U3 Communications
CMR
The 1U4 has det. a loss of IPC comm from the 1U3 module.
U4 Indicating U5 Communications
CMR
The 1U4 has det. a loss of IPC comm from the 1U5 module.
U5 Indicating U1 Communications
CMR
The 1U5 has det. a loss of IPC corn from the 1U1 module.
U5 Indicating U3 Communications
CMR
The 1U5 has det. a loss of IPC corn from the 1U3 module.
U5 Indicating U4 Communications
CMR
The 1U5 has det. a loss of IPC comm from the 1U4 module.
U6 Indicating U1 Communications
CMR
The 1U6 has det. a loss of IPC comm from the 1U1 module.
U6 Indicating U3 Communications
CMR
The 1U6 has det. a loss of IPC comm from the 1U3 module.
U6 Indicating U7 Communications
CMR
The 1U6 has det. a loss of IPC comm from the 1U7 module.
Winding Temp - Cprsr A
CMR
a.
The motor winding temperature thermostat opened;
nominally 221 F.
b.
The motor temp. thermostat or wiring is open.
c.
Time to trip from input open to compressor shutdown
shall be 0.5 to 2.0 seconds.
Table 28
Diagnostic Codes
Diagnostic Description
Type
Cause
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...