Controls Interface
Leaving Water Temperature Cutout
This temperature cutout provides protection against freezing caused by low
leaving water temperature. The setpoint is both factory set and adjustable
from the Service Settings Menu. Temperatures below the setpoint will cause
the UCM to accelerate reduction of chiller capacity, even to the point of
compressor shutdown. A non-latching diagnostic will be generated if the LWT
is below the cutout for more than 30 degree F seconds.
There must be a minimum of 5 F between the cutout temperature and both
the front panel and active chilled water setpoints. The Clear Language Display
will not permit setting of either the front panel or active chilled water temper-
atures less than 5 F above this cutout temperature. The second line will state
“Limited by Cutout Setpoint, (+) to change”.
If the leaving water temperature cutout is set upward, the Clear Language
Display will maintain the 5 F minimum and will automatically raise the
settings on the front panel and active chilled water setpoints, if necessary.
If the front panel or Active Chilled Water Setpoints were adjusted, the display
will show the following when the “Enter” key is pressed:
“FRONT PANEL CHILLED WATER SETPOINT
HAS BEEN INCREMENTED DUE TO CUTOUT
SETPOINT CHANGE”
If the leaving water temperature drops below the cutout setpoint while the
compressors are de-energized, it will produce an IFW diagnostic. If the
leaving water temperature drops below the cutout setpoint while the
compressors are energized for 30 F seconds, the unit will shut down on an
MAR diagnostic.
Low Refrigerant Temperature Cutout
Both circuits are protected from a saturated evaporator refrigerant temper-
ature that goes below this setting. The cutout setpoint must be a minimum of
15 F lower than the front panel or active chilled water setpoints. See
Table 26
for proper settings.
There must be a minimum of 15 F between the cutout temperature and both
the front panel and active chilled water setpoints. The Clear Language Display
will not permit setting of either the front panel or active chilled water temper-
atures less than 15 F above this cutout temperature and the display will flash
the last valid temperature.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...