146
RLC-SVX07A-EN
Diagnostics
In the table below, a latching diagnostic is a condition which shall cause the
machine or a portion of the machine as noted to shut down and shall require a
manual reset to restore operation. A diagnostic that is non-latching shall reset
automatically when the condition causing the diagnostic goes away. A non-
latching diagnostic shall shut down the machine or a part of the machine if so
indicated. If a diagnostic is informative only, no machine or circuit action is
taken except to load a diagnostic code into the last diagnostic register.
Diagnostic Types (And Action)
MMR = Machine Shutdown, Manual Reset
MAR = Machine Shutdown, Auto Reset
CMR = Circuit Shutdown, Manual Reset
CAR = Circuit Shutdown, Auto Reset
IFW = Information Warning
Table 28
Diagnostic Codes
Diagnostic Description
Type
Cause
Chilled Water Flow (Ent Wtr Temp)
MMR
a.
The entering evaporator water temp. fell below the
leaving evaporator water temp. by more than 2F for 100
degree F - seconds.
b.
Causes to trip this diagnostic include either a loss of
chilled water flow or a calibration shift in the evap. water
temp. sensors.
Chilled Water Flow Interlock
MAR
The chilled water flow switch input was open for more than 6
seconds.
Compressor Overload Setting Cprsr A
IFW
The CPM NovRam Based overload setting did not agree with
the MCSP Dip Switch overload setting for 30 contiguous
seconds. The affected MCSP shall use the minimum (00000
binary, 00 decimal) overload setting as a default until the UCM
is reset when this diagnostic occurs.
Compressor Overload Setting - Cprsr B
I FW
Same as Cprsr A, above.
Compressor Overload Setting - Cprsr C
IFW
Same as Cprsr A, above.
Compressor Overload Setting - Cprsr D
IFW
Same as Cprsr A, above.
Cond Fan Var Speed Drive Fault Ckt 1
IFW
The controlling MCSP for the given circuit has unsuccessfully
attempted (5 times within 1 minute) to clear a fault signal from
the Condenser Fan Inverter Drive. The 5th attempt removes
power from the inverter to create a power up reset. If the fault
does not clear, the UCM will revert to constant speed
operation without the use of the inverters fan. The inverter
must be manually bypassed for full fixed speed fan operation.
Cond Fan Var Speed Drive Fault Ckt 2
IFW
Same as Ckt 1, above.
Cond Entering Wtr Temp Sensor
IFW
Shorted Cond. temp sensor. No diagnostic on open.
Cond Leaving Wtr Temp Sensor
IFW
Shorted Cond. temp sensor. No diagnostic on open.
Cond Rfgt Temp Sensor - CKT 1
CMR
Open or short.
Cond Rfgt Temp Sensor - CKT 2
CMR
Open or short.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...