RLC-SVX07A-EN
9
General Information
Installation Responsibilities
Generally, the contractor must install the unit per the instructions contained in
Sections 2 and 3 of this manual, including the following:
•
Install unit on a flat foundation, level (within 1/4” [6.4 mm]), and strong
enough to support unit loading.
•
Install any optional sensors and make electrical connections at the Unit
Control Panel.
NOTE:
The standard leaving chilled water sensor is factory installed in the
evaporator leaving water outlet.
•
Where specified, provide and install valves in water piping upstream and
downstream of evaporator and condenser water connections to isolate
Table 4
General Data RTAC Air-Cooled Condenser
Size
70
80
90
100
110
125
Condenser
Qty. of Coils
4
4
4
4
4
4
Coil Length
1
(In)
156/156
156/156
168/156
168/168
204/168
204/204
Coil Height
(In)
42
42
42
42
42
42
Number of Rows
2
2
2
2
2
2
Condenser Fans
Quantity (1)
4/4
4/4
5/4
5/5
5/5
5/5
Diameter
(In)
30
30
30
30
30
30
Total Airflow
(CFM)
71750
71750
77640
83530
87505
91480
Nominal RPM
850
850
850
850
850
850
Tip Speed
(Ft. Min)
6675
6675
6675
6675
6675
6675
Motor SP
(Ea)
1.1
1.1
1.1
1.1
1.1
1.1
Min. Starting/Oper.
Ambient
2
HCFC-22
HCFC-22
HCFC-22
HCFC-22
HCFC-22
HCFC-22
Std Unit
(Deg F)
15
15
15
15
15
15
Low Ambient
(Deg F)
-10
-10
-10
-10
-10
-10
Weights
Operating Wt.
(Lbs)
3384
3384
3625
3686
3941
4110
(Kg)
1535
1535
1645
1671
1788
1865
Shipping Wt.
(Lbs)
3303
3303
3531
3584
3821
3973
(Kg)
1500
1500
1603
1627
1735
1804
Overall Dim.
(in)
Length
204
204
204
204
231
231
Width
85
85
85
85
85
85
Height
88
88
88
88
88
88
Overall Dimensions
(mm)
Length
5176
5176
5176
5176
5861
5861
Width
2240
2240
2240
2240
2240
2240
Height
2223
2223
2223
2223
2223
2223
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operating ambient based on a 5 mph wind across the condenser.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...