RLC-SVX07A-EN
Installation - Remote Condenser
CAUTION
Catastrophic Damage!
Tables
8
,
9
and
10
show line sizing for leaving evaporator water
temperatures ranging from 0 F to 60 F. Only units with a “2” or
“4” in the 12th digit of the model number of the RTUA unit can be
piped using Tables
8
and Unless the RTUA unit is designed for
low temperature applications, Table
8
must be used. Catastrophic
damage may result if the incorrect table is used for pipe sizing.
2.
The total distance between the RTUA and the aircooled condenser must
not exceed 200 actual feet or 300 equivalent feet.
3.
Liquid line risers must not exceed 15 feet from the base of the air-cooled
condenser.
4.
Discharge line risers cannot exceed an elevation difference greater than
100 actual feet without a minimum of 2% efficiency decrease.
5.
Refer to
Figures
23
,
24
and
25
for location of recommended traps.
6.
Circuit #1 on the condenser must be connected to Circuit # 1 on the
RTUA unit.
CAUTION
Equipment Damage!
If circuits are crossed, serious equipment damage may occur.
NOTE:
The piping shown in
Figures
23
,
24
and
25
are for one circuit only.
The piping for the other circuit should follow the same guidelines.
Equivalent Line Length
To determine the appropriate size for field installed liquid and discharge lines,
it is first necessary to establish the equivalent length of pipe for each line,
including the added flow resistance of elbows, valves, etc. An initial approxi-
mation can be made by assuming that the equivalent length of pipe is 1.5
times the actual pipe length.
It is also necessary to know the capacity (tons) for each circuit. Circuit capac-
ities for each RTUA unit are listed in
Table
6
.
Table 6
RTUA Circuit Capacities
MODEL CIRCUIT 1
CIRCUIT 2
70
35
35
80
40
40
90
50
40
100
50
50
110
60
50
125
60
60
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...