RLC-SVX07A-EN
43
Installation - Mechanical
CAUTION
Equipment Damage!
To prevent capacity reduction and relief valve damage, do not
exceed vent piping code specifications.
Relief valve discharge setpoints are 450 psig. Once the relief valve has
opened, it will reclose when pressure is reduced to a safe level.
Pipe each relief valve on the unit into a common vent line. Provide access
valve located at the low point of the vent piping, to enable draining of any
condensate that may accumulate in the piping.
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover
refrigerant to relieve pressure before opening the system. See
unit nameplate for refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved
refrigerants, refrigerant substitutes, or refrigerant additives could
result in death or serious injury or equipment damage.
If multiple chillers are installed, each unit must have a separate venting for its
relief valves. Consult local regulations for any special relief line requirements.
Evaporator Pressure Relief Valve Venting (for RTWA and RTUA
units only)
All RTWA and RTUA units utilize a low-side refrigerant-pressure relief valve for
each circuit which must be vented to the outdoor atmosphere. The valves are
located on the refrigerant head of the evaporator, one per circuit. Relief valve
connections are 3/8” flare. Refer to Figure
21
and Table
5
. Refer to local
codes for relief valve vent line sizing requirements.
NOTE:
Vent line length must not exceed code recommendations. If the line
length will exceed code recommendations for the outlet size of the valve,
install a vent line of the next larger pipe size.
Table 5
Relief Valve Descriptions
Relief Setpoint
450 psig
300 psig
Units
RTWA/RTUA
RTWA/RTUA
Quantity
1 per ckt
1 per ckt
Relief Rate
Superior
Henry
N/A
35.8lba/min
10.21 Iba/min
N/A
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...