RLC-SVX07A-EN
121
Controls Interface
2-10 VDC/4-20 mA Input for External Chilled Water Setpoint (CWS) and
Current Limit Setpoint (CLS)
When either external CWS or external CLS is used on the optional Module
1U2, DIP switch SW1 positions 1 and/or 2 must be set to accommodate the
type of signal source the customer has chosen, either 2-10 VDC or 4-20 mA.
Position SW-1-1 sets 2-10 VDC/4-20 mA for external CWS. SW1-2 sets 2-10
VDC/4-20 mA for external CLS. The “OFF” setting configures the external
input for 2-10 VDC; the “ON” setting configures the external input for
4-20 mA.
Mechanical Control Settings
The settings for the High Pressure switch, Oil Pressure switch, and Winding
Thermostat are shown below:
Remote CLD Operation
With only few exceptions, operation of the Remote CLD is identical to the
unit's CLD. To ease the operation of the Remote CLD, additional displays have
been added. For example, if multiple unit operation is used, the following
display will be inserted as the second display of the setpoint group:
Modify Setpoints for Units X
“Press (+) (-) to change settings”
The Stop and Auto keys function in the same manner, but the following
hierarchy between the unit's Stop/Auto keys and the Remote CLD Stop/Auto
keys is as follows:
1.
Local Stop will always override Local Auto, Remote Stop and
Remote Auto.
2.
Local Auto will always override Local Stop, Remote Stop and
Remote Auto.
3.
Remote Stop will override Local Auto and Remote Auto but not
Local Stop.
4.
Remote Auto will override Local Auto and Remote Stop but not
Local Stop.
If an operator tries to start the unit from the Remote CLD after the Stop
command has been given at the unit CLD, the screen on the Remote CLD will
read:
“LOCAL STOP command at unit cannot be
overridden by this remote device”
Communication Failure
If a communication failure occurs between the Remote CLD and the unit's
CLD, the setpoints will remain the same but a diagnostic will occur at the
Remote CLD panel. The Remote display screen will read:
“No communication to Unit X”
Press (enter) to select new unit
IPC DIP
SWITCH
MODULE
1U3
1U4
1 US
1U7
1
OFF
OFF
OFF
OFF
2
OFF
OFF
ON
OFF
3
—
—
—
ON
CLOSE
OPEN
Compressor Discharge High Pressure Switch – PSIG
300 ±20
405 ±7
Compressor Motor Winding Thermostat – F
181
221
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...