RLC-SVX07A-EN
143
Refrigerant Charging
If the refrigerant charge needs to be adjusted, be certain to monitor the
subcooling and superheat measurements. The subcooling needs to be
between 6 F and 8 F when the unit is running fully loaded. The ambient
temperature is between 75 F and 100 F and the leaving water temperature is
between 40 F and 55 F. The superheat needs to be close to or at the
superheat setpoint entered in the UCM.
CAUTION:
Equipment Damage!
The evaporator water flow must be established and maintained
while adjusting the charge. Refrigerant pressures below 65 psig
can cause freezing and rupturing of the evaporator tubes.
Adding Refrigerant
The RTWA 70-125 ton units are shipped with an entire charge of refrigerant
and oil. The RTUA 70125 ton units are shipped with a holding charge of
nitrogen and the oil charge, excluding the additional oil charge needed for field
piping. If the unit has no pressure, the system must be leak tested prior to
adding refrigerant. Evacuate the system down to at least 100 microns prior to
adding the refrigerant.
CAUTION:
Equipment Damage!
Water must be flowing through the tube bundles during this
entire process. Refrigerant pressures below 65 psig can cause
freezing and rupturing of the heat exchangers.
1.
Connect 115 VAC power to the master solenoid, the female load solenoid
and the male load/unload solenoids. This must be done to evacuate all of
the cavities in the compressor.
2.
Open all service valves.
3.
Connect hoses from the vacuum pump to the backseat ports on the suc-
tion line service valve and the discharge line service valve.
4.
Evacuate the system to 100 microns and isolate the vacuum pump.
5.
Confirm that no moisture or leaks are present by letting the vacuum stand
for several minutes.
6.
Add refrigerant gas to the system through the backseat port on the dis-
charge service valve until the pressure is above 65 psig.
NOTE:
Weigh in entire charge from
Table
1
(RTWA only) and Paragraph
"Remote Air-Cooled Condenser Interconnecting Refrigerant Piping" on Page
45
(RTUA and RTCA units).
7.
Once the pressure exceeds 65 psig, add liquid refrigerant through the 1/4
inch service valve between the EXV and the evaporator.
8.
The unit may need to be started to add the entire charge. Once the unit is
started, monitor the subcooling and superheat to trim the charge.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...