RLC-SVX07A-EN
119
Controls Interface
Phase Imbalance Protection
The Clear Language Display monitors the current in each phase and calcu-
lates the percentage of imbalance as follows:
= phase with greatest difference from lave (without regard to sign)
If Phase Unbalanced Protection (Service Settings Menu) is enabled, and the
average three phase current is greater than 80% RLA, and the percent of
imbalance is calculated to exceed 15%, the UCM will shutdown the
compressor and display a CMR diagnostic.
In addition to the 15% criteria, the Clear Language Display has a non-
defeatable 30% criteria which has its own diagnostic. If the 15% criteria is
enabled, it will always display the 15% diagnostic first. The 30% criteria is
always active when a compressor is running, regardless of% RLA.
Reverse Rotation Protection
The Clear Language Display monitors incoming current during start-up and
will shutdown the compressor within one second, if phase reversal is
detected.
CAUTION
Reversed Phase Rotation!
Phase relationships during installation of unit power must be
carefully controlled to assure compressor protection against
reversed phase rotation. See Installation - Electrical.
Oil Failure Protection
The 70 to 125 Ton units no longer use the differential pressure switch to
monitor for an oil line restriction. The logic of the UCM uses a comparison of
the entering oil temperature at the compressor to the saturated condenser
temperature to determine if there is an oil line restriction.
The differential between the entering oil temperature and the saturated
condenser temperature is referred to as the” Oil Loss Differential Setpoint” in
the Service Settings Menu. This setpoint must remain at the default of -4 F
for the unit to function properly.
If the entering oil temperature drops 4 F below the saturated condenser
temperature for more than 30 minutes, the circuit will shutdown on a CMR
diagnostic. The diagnostic will be presented as:
“OIL SYSTEM FAULT - CKT X°
% Imbalance
l
x
l
ave
–
(
)
x 100
l
ave
-------------------------------------
=
l
ave
l
1
l
2
l
3
+
+
(
)
3
------------------------------
=
1
x
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...