RLC-SVX07A-EN
123
Pre-Start Checkout
•
Fill the evaporator and condenser chilled water circuits. Refer to Table
1
for liquid capacities. Vent the system while it is being filled. Open the
vents on the top of the evaporator and condenser during filling and close
when filling is completed.
Customer Note
The use of improperly treated or untreated water in this equipment may
result in scaling, erosion, corrosion, algae or slime. The services of a qualified
water treatment specialist should be engaged to determine what treatment,
if any, is advisable. The Trane Company warranty specifically excludes liability
of corrosion, erosion or deterioration of Trane equipment. Trane assumes no
responsibilities for the results of the use of untreated or improperly treated
water or saline or brackish water.
CAUTION:
Equipment Damage!
Do not use untreated or improperly treated water. Equipment
damage may occur.
•
Close the fused-disconnect switch(es) that supplies power to the chilled
water pump starter and the condenser water pump starter.
•
For RTCA units, close the fused-disconnect switches that supply power
to the fans.
•
Start the chilled water pump and condenser water pump to begin circula-
tion of the water. Inspect all piping for leakage and make any necessary
repairs.
•
With water circulating through the system, adjust water flow and check
water pressure drop through the evaporator and condenser. Refer to
Figures
16
,
17
and
18
.
•
Adjust the chilled water flow switch and condenser water flow switch (if
installed) for proper operation.
•
Prove all Interlock and Interconnecting Wiring Interlock and External as
described in Section
“Installation - Electrical”
.
•
Check and set, as required, all Clear Language Display Menu Items.
•
Stop the chilled water pump and condenser water pump.
Unit Voltage Power Supply
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...