RLC-SVX07A-EN
127
Start-Up Procedures
If the pre-start checkout, as discussed above, has been completed, the unit is
ready to start. The Clear Language Display is shown in
Figure
39
and Clear
Language Display Sequence of Operation is shown in
Figure 41
. Complete
each step, in sequence, as follows:
•
Press the Stop key on the Clear Language Display.
•
As necessary, adjust the setpoint values in the Clear Language Display
menus, as described in Paragraph
"Clear Language Display Keypad Over-
view" on Page 91
.
•
Close the fused-disconnect switch for the chilled water pump and con-
denser water pump. Energize the pumps to start water circulation.
•
Check the service valves on the discharge line, suction line, oil line and
liquid line for each circuit. These valves must be open (backseated) before
starting the compressors.
CAUTION:
Compressor Damage!
To prevent compressor damage, do not operate the unit until all
refrigerant and oil line service valves are opened.
•
Verify that the chilled water pump runs for one minute after the chiller is
commanded to stop (for normal chilled water systems). See Paragraph
"Interconnecting Wiring" on Page 62
.
•
Press the Auto key. If the chiller control calls for cooling and all safety
interlocks are closed, the unit will start. The compressor(s) will load and
unload in response to the temperature of the leaving chilled water tem-
perature.
Once the system has been operating for approximately 30 minutes and has
become stabilized, complete the start-up procedures, as follows:
•
Check the evaporator refrigerant pressure and the condenser refrigerant
pressure under Refrigerant Report on the Clear Language Display. The
pressures are referenced to sea level (14.6960 psia).
•
Check the liquid line sight glasses. The refrigerant flow past the sight
glasses should be clear. Bubbles in the refrigerant indicate either low
refrigerant charge or excessive pressure drop in the liquid line. A restric-
tion in the line can sometimes be identified by a noticeable temperature
differential between the two sides of the restriction. Frost may often form
on the line at this point. Proper refrigerant charges are shown in
Table
1
.
NOTE:
A clear sight glass alone does not mean that the system is properly
charged. Also check system superheat, subcooling, and unit operating
pressures.
•
Measure the system superheat. Refer to Paragraph
"System Superheat"
on Page 128
.
•
Measure the system subcooling. Refer to Paragraph
"System Subcooling"
on Page 128
.
•
A shortage of refrigerant is indicated if operating pressures are low and
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...