10
RLC-SVX07A-EN
General Information
the heat exchangers for maintenance, and to balance/trim system.
•
If desired, supply and install flow switches in both the chilled water and
condenser water piping; interlock each switch with proper pump starter
to ensure unit can only operate if water flow is established. Chilled water
flow protection is provided by the Unit Controls without the need for a
chilled water flow switch. A flow switch for chilled water is strictly discre-
tionary.
•
Furnish and install pressure gauges in inlet and outlet piping of the evapo-
rator and condenser.
•
Furnish and install a drain valve to both the evaporator and condenser.
•
Supply and install a vent cock to the top of the evaporator and condenser.
•
Furnish and install strainers ahead of all pumps and automatic modulating
valves.
•
Provide and install field wiring.
•
Start unit under supervision of a qualified service technician.
Nameplates
The RTWA/RTUA unit nameplates (
Figure 1
) are applied to the exterior
surface of the Control Panel door.
A compressor nameplate is located on each compressor. The RTCA unit
nameplate is applied to the side of the control panel.
Unit Nameplate
The unit nameplate provides the following information:
•
Unit model and size descriptor.
•
Unit serial number.
•
Identifies unit electrical requirements.
•
Lists correct operating charges of R-22 and refrigerant oil.
•
Lists unit test pressures
•
Identifies installation, operation and maintenance and service data litera-
ture.
•
Lists drawing numbers for unit wiring diagrams.
Compressor Nameplate
The compressor nameplate provides the following information:
•
Compressor model number.
•
Compressor serial number.
•
Compressor electrical characteristics.
•
Utilization Range.
•
Recommended refrigerant.
ASME Nameplate
The ASME Nameplate is different for the evaporators and condensers (RTWA
only). The evaporator nameplate is located on the tubesheet, on the suction
end. The insulation over the nameplate is intentionally left unglued, for ease in
viewing the nameplate.
Each condensing shell has a nameplate located on the top of the shell,
between the relief valve and the tubesheet. The nameplates are at opposite
ends from each other.
Summary of Contents for R Series
Page 17: ...RLC SVX07A EN 17 Installation Mechanical Figure 2 Rigging and Lifting for RTWA Units ...
Page 22: ...22 RLC SVX07A EN Installation Mechanical Figure 7 Rigging and Lifting for RTUA Units ...
Page 25: ...RLC SVX07A EN 25 Installation Mechanical Figure 10 Rigging and Lifting for RTCA Condenser ...
Page 69: ...RLC SVX07A EN 69 Installation Electrical Figure 28 Interconnecting Wiring from RTUA to RTCA ...
Page 129: ...RLC SVX07A EN 129 Start Up Procedures Figure 41 RTWA Unit Sequence of Operation ...
Page 130: ...130 RLC SVX07A EN Start Up Procedures Figure 42 RTUA Unit Sequence of Operation ...
Page 154: ...154 RLC SVX07A EN Diagnostics ...
Page 156: ...156 RLC SVX07A EN 3332 ...
Page 158: ...158 RLC SVX07A EN 3333 ...
Page 160: ...160 RLC SVX07A EN 3334 ...
Page 162: ...162 RLC SVX07A EN 3335 ...
Page 164: ...164 RLC SVX07A EN 3336 ...
Page 166: ...166 RLC SVX07A EN 5119 ...
Page 168: ...168 RLC SVX07A EN 5143 ...
Page 170: ...170 RLC SVX07A EN 5144 ...
Page 172: ...172 RLC SVX07A EN 5145 ...
Page 174: ...174 RLC SVX07A EN 5146 ...
Page 176: ...176 RLC SVX07A EN 6008 ...
Page 178: ...178 RLC SVX07A EN 6009 ...
Page 180: ...180 RLC SVX07A EN 5147 ...
Page 182: ...182 RLC SVX07A EN 6526 ...
Page 184: ...184 RLC SVX07A EN 5150 ...
Page 186: ...186 RLC SVX07A EN 6010 ...