410
Solar-Log™ PRO
4 Solar-Log™ PRO
4.1
Solar-Log™ PRO1 Mod (single phase)
Selections available under „Solar-Log/Pro/RS485“
Supported by firmware 4.1.0 and higher
Overview
•
The communication address has to be assigned.
•
2-pin wiring.
•
Installation steps:
•
Switch off the meter and the Solar-Log™.
•
Connect the meter to the Solar-Log™.
Note
The communication address is set to 1 by default, but can be adjusted
if several meters are connected to one RS485 bus.
Maximum of 60 meters per RS485 bus.
Connect the meter to the Solar-Log™
The wiring is done using a
•
self-made cable connection with a terminal block connector.
4.1.1
Connection diagram
According to circuit type 1000 (DIN 43856)
L-IN Terminal 1
Supply line input phase „L1“
L-OUT Terminal 3
Supply line output phase „L1“
Terminal 4 „N“
Neutral conductor connection „N“
Terminal 6 „N“
Neutral conductor connection „N“
Terminal 20, 21
S
0
pulse output
Terminal 23,24
ModBus connection terminal 23 -> A, 24 -> B
Fig.: Pin assignment
Summary of Contents for Solar-Log
Page 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Page 20: ...20 01 Inverter ...
Page 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Page 402: ...402 02 Meter ...
Page 444: ...444 03 Battery Systems ...
Page 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Page 463: ...463 04 Heating rods ...
Page 470: ...470 05 Heating pumps ...
Page 478: ...478 06 Sensors ...
Page 488: ...488 07 Pyranometer ...
Page 495: ...495 08 Smart Plug components ...
Page 502: ...502 09 Power Charging Stations ...