Shindengen
Procedure
1. Open the inverter as shown in the inverter’s instructions.
2. If you are fabricating the cable yourself, connect the wires as shown in the following diagram.
Terminal strip inside the inverter
Terminal strip inside the inverter
RS485 terminal
RS485 terminal
►
30 A (+)
►
30 A (+)
►
31 GND
►
31 GND
►
13 B (-)
►
13 B (-)
3. Connect terminals on inverter 1 to the corresponding terminals on inverter 2.
4. Connect the other inverters to each other in the same way.
5. If no further inverter is connected, terminate the inverter according to the instructions for the inverter.
6. Close inverters.
7. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Allocate communication address
•
Recommendation: Continuous numbering from 1 to 30
•
Procedure: Start according to the inverter’s instructions.
Note
A maximum of 30 inverters can be connected per RS485 bus.