194
Kostal and Solar-Fabrik
Note
Each inverter must be accessible through the network individually.
It is thereby necessary to activate the network interface on each inverter (under the menu item “LAN”
select “Activate LAN”) and to connect the inverters to the network by means of a switch.
Detection via the Solar-Log™ WEB Interface
•
For detection on the Solar-Log™ , select the device class under the menu Configuration | Device | Definition |
Interface with the plus symbol and then select Kostal as the manufacturer. Confirm your selection with OK.
•
Save your selections and then start the Device Detection under Configuration | Device | Detection.
Detection from the Solar-Log 1200
•
When using the Solar-Log 1200, the detection can also be started from the display. Select the settings ►Start
►
Initial Configuration
►
Page 2 „Device“
►
Add and select the manufacturer Kostal from there. Save and
start the Device Detection.
Note Power Management (Inverter Settings):
The power reduction function is only available when the “Sensors” selection has been activated under
the -> Settings / Analog Inputs menu.
In order that reactive power control functions, the low-voltage guidelines have to be selected in the
country settings for the inverter (e.g. "DE-NSR" for the German low-voltage guidelines).
Caution:
The country settings can only be configured once during the initial installation. If the wrong country
is selected, it can be reset using the Kostal software tool "PARAKO." This tool can be obtained directly
from Kostal after registering.
Summary of Contents for Solar-Log
Page 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Page 20: ...20 01 Inverter ...
Page 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Page 402: ...402 02 Meter ...
Page 444: ...444 03 Battery Systems ...
Page 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Page 463: ...463 04 Heating rods ...
Page 470: ...470 05 Heating pumps ...
Page 478: ...478 06 Sensors ...
Page 488: ...488 07 Pyranometer ...
Page 495: ...495 08 Smart Plug components ...
Page 502: ...502 09 Power Charging Stations ...